A single monitor method for voltage sag source location using hilbert huang transform

Wong Ling Ai, Hussain Shareef

Research output: Contribution to journalArticlepeer-review

10 Citations (Scopus)

Abstract

This study introduces a method for voltage sag source location based on Hilbert Huang transformed monitored current signal. Unlike the traditional method, the proposed method first transforms the recorded current during the sag event to obtain frequency-time plot (Hilbert spectra) and IMF plot before the location of voltage sag source is determined. Then based on the change in frequency and IMF the relative location of voltage sag source is obtained. The effectiveness of the proposed method has been verified through simulation on 20 bus system and by comparing with an existing S-Transform based method. The results show that the presented method can determine the location of voltage sag source correctly.

Original languageEnglish
Pages (from-to)192-202
Number of pages11
JournalResearch Journal of Applied Sciences, Engineering and Technology
Volume5
Issue number1
DOIs
Publication statusPublished - 2013
Externally publishedYes

Keywords

  • Hilbert huang transform
  • Power quality
  • Signal processing
  • Voltage sags

ASJC Scopus subject areas

  • Computer Science(all)
  • Engineering(all)

Fingerprint

Dive into the research topics of 'A single monitor method for voltage sag source location using hilbert huang transform'. Together they form a unique fingerprint.

Cite this